Air Cooled Single Compressor Screw (heat) Chiller
Weiwei new Wood Chipper with gasoline engine machine is especially suitable for small families, garden pruning, branch crushing and so on, the chipper can be cut and crushed small diameter wood, garden pruning waste branch, branch, bamboo, grapevine, corn stalk, rapeseed pole, honeysuckle branch, etc.
wood chipper ,wood shredder ,wood cutting Zhengzhou WeiWei Machinery Co., LTD. , https://www.weiweimachine.com
Features
1.World famous brand new type and high-efficient screw-rotor compressor, with efficiency 20%~30% higher than those common ones. It has obtained several patents of Europe and America countries and passed the international quality certification of ISO9001.
2.High efficiency 5-to-6 rotor profile patent.
3.Capacity control apply to four-step (100%-75%-50%-25%),three-step (100%-66%-33%) and no step control system.
4.With 11 bearings and a balance piston against axial thrust. This extends longer bearings life 2.5 to 3.5 times than traditional design.
5.Designed with efficient silicon steel and special slots , and equipped with the inside and outside all around design to cool the flow channel so to ensure maximum efficiency of the compressor motor under any load.
6.Built-in oil pressing system ensure compressor maintaining the optimal lubricity without oil pump.
7.High efficiency double filtration oil separator ensures maxinum heat exchanger.
8.Efficient, low noise and small vibration.
9.Various options of refrigerants, R22, environment-friendly R134A, R407C etc.
10.All-wave compressor volume ratio(Vi=2.2/2.6/3.0/3.5) for selection to avoid the extra energy consumption caused by over or under compression.
Â
Model list
Model  Item
040WSH
050WSH
060WSH
075WSH
085WSH
100WSH
120WSH
Nominal cooling
capacity
kcal/h
103888
130204
152564
212420
241660
276060
342280
kw
120.8
151.4
177.4
247
281
321
398
Total input power
kw
30.9
37.9
43.3
56.8
65
74
90.3
Max.Running current
A
71
84
128
123
140
160
195
Power
Â
3PH-380V-50HZ(200V/220V/415V 50HZ/60HZ)
Refrigerant
Type
Â
R22
Refrigerant
charge
kg
22
27
33
42
48
55
68
Control method
Â
thermostatic expansion valve
Compressor
Type
Â
Semi-hermetic screw
Power
kw
30.9
37.9
43.3
56.8
65
74
90.3
Start-up mode
Â
Y-â–³
Capacity control
%
0-25-50-75-100
Evaporator
Type
Â
Shell and Tube
Chilled fluid flow
m3/h
20.7
26.0
30.4
42.3
48.2
55.0
68.2
Inlet/outlet
pipe diameter
Inch
3"
3"
3"
3"
4"
4"
4"
Condenser
Type
Â
Shell and Tube
Â
Cooling water flow
m3/h
26.0
32.5
37.8
52.1
59.3
67.7
83.7
Â
Â
Inlet/outlet pipe caliber
Inch
3"
3"
3"
3"
4"
4"
4"
Â
Â
Safety protection
Compressor over temperature,over current,high and low pressure,over temperature,flow switch,
phase sequence,phase-missing,exhaust Overheating,anti-freezing.
Â
Dimension
Length
mm
1960
2130
2450
2450
2750
2750
2750
Â
Â
Width
mm
855
855
985
985
1050
1050
1050
Â
Â
Height
mm
1540
1540
1600
1600
1600
1600
1730
Â
Â
Net weight
Â
820
950
1120
1300
1560
1720
2030
Â
Â
Running weight
Â
970
1060
1270
1480
1780
1960
2250
Â
Â
Â
Â
Â
Â
Â
Â
Â
Â
Â
Â
Â
1.Transportation of unit
(1). The chiller is packed in standard wooden box. We suggest hoisting if conditions warrant it. The forklift can be used during ground transportation. If the hoisting is made after the removal of packaging, pay attention not to put too much pressure on the chiller box. If necessary with the supporting rod to hoist.
(2). The units with wheel can be rolled on the ground and the units must keep balance
(3). Whatever way to transport, it must be carefully not to sway over not to collide so as not to damage
the equipment or endanger the safety of people.
★Not to use the forklift to transport the units after the package removed!
2.Installation of unit
(1).How to choose the installation location
Unit suitable for installation in the ambient temperature of -10~43 degrees, relative humidity of not more than 80% of the rain-proof shelter, or with the external environment has good ventilation conditions of indoor. In the wind direction is not less than 2meters of space, in a side condenser inlet wind direction should have 1.5~2meters of space. Units to be placed in no less than 20cm level solid concrete foundation, DLP-10AS and larger units with damping device, using the anchor bolt. Around the unit should have a working space, to facilitate the operation, inspection and maintenance.
Â